| Product Characteristics |
| Process Connection | G 2 DN50 external thread |
| System | Gold-plated contacts |
| Media | Ultra-pure water; water; water-based media |
| Medium Temperature [° C] | -20 - 100 |
| Vacuum Resistance [mbar] | -1000 |
| MAWP (for Applications According to CRN) [bar] | 100 |
| Electrical Data |
| Operating Voltage [V] | 18 - 32 DC; (to SELV/PELV) |
| Current Consumption [mA] | < 75 |
| Protection Class | III |
| Reverse Polarity Protection | Yes |
| Power-on Delay Time [s] | 5 |
| Measuring Principle | Ultrasonic |
| Inputs |
| Inputs | Counter reset |
| Outputs |
| Total Number of Outputs | 2 |
| Output Signal | Switching signal; pulse signal; analog signal; IO-Link; frequency signal; diagnostic signal; totalizer switching signal |
| Electrical Design | PNP/NPN |
| Output Function | Normally open / closed; (configurable) |
| Maximum Voltage Drop Switching Output DC [V] | 2 |
| Permanent Current Rating of Switching Output DC [mA] | 100 |
| Switching Frequency DC [Hz] | 0 - 10000 |
| Analog Current Output [mA] | 4 - 20 |
| Maximum Load [Ω ] | 500 |
| Pulse output | Flow rate meter |
| Short-Circuit Protection | Yes |
| Type of Short-Circuit Protection | Yes (non-latching) |
| Overload Protection | Yes |
| Measuring/Setting Range |
| Frequency at the end point FRP [Hz] | 1 - 10000 |
| Volumetric flow quantity monitoring |
| Pulse length [s] | 0.002 - 2 |
| Pulse value | 0.1 - 99990000 I |
| Temperature Monitoring |
| Measuring Range [° C] | -20 - 100 |
| Display range [° C] | -44 - 124 |
| Resolution [° C] | 0.1 |
| Set point SP [° C] | -19.6 - 100 |
| Reset point rP [° C] | -20 - 99.6 |
| Analog Start Point [° C] | -20 - 76 |
| Analog End Point [° C] | 4 - 100 |
| Frequency start point, FSP [° C] | -20 - 76 |
| Frequency end point, FEP [° C] | 4 - 100 |
| Frequency at the end point FRP [Hz] | 1 - 10000 |
| Accuracy / deviations Flow monitoring |
| Accuracy (in the Measuring Range) | ± (1,0 % MW + 0,5 % MEW) |
| Repeatability | ± 0,2 % MEW |
| Temperature Monitoring |
| Accuracy [K] | ± 2,5 (Q>5 % MEW) |
| Temperature coefficient [% of the span / 10 K] | 0,2 |
| Reaction Times Flow monitoring |
| Response Time [s] | < 0.25; (dAP = 0, T09) |
| Damping Process Value dAP [s] | 0 - 5 |
| Temperature Monitoring |
| Dynamic Response T05 / T09 [s] | 5,7 / 86 |
| Software / Programming |
| Diagnostic functions | Direction of flow detection; signal quality |
| Interfaces |
| Communication Interface | IO-Link |
| Transmission Type | COM2 (38,4 kBaud) |
| IO-Link Revision | 1.1.3 |
| SDCI Standard | IEC 61131-9: 2013-07 |
| Profiles | Identification and Diagnosis (0x4000) |
| Required Master Port Class | A |
| Process Data Analog | 3 |
| Process Data Binary | 2 |
| Minimum Process Cycle Time [ms] | 9.6 |
| Operating Conditions |
| Ambient Temperature [° C] | -20 - 60 |
| Storage Temperature [° C] | -25 - 80 |
| Protection | IP 67 |
| MTTF [Years] | 160 |
| Pressure Equipment Directive | Can be used for group 2 fluids; group 1 fluids on request |
| Mechanical Data |
| Weight [g] | 1180 |
| Type of Mounting | Inlet pipe length 5xDN; outlet pipe length 1xDN |
| Material | Housing: stainless steel (1.4404 / 316L); Display: PFA; sealing Display: FKM; connector: POKAN |
| Materials (Wetted Parts) | Pipe section: stainless steel (1.4404 / 316L); Process Connection sealing: Centellen Gasket |
| Process Connection | G 2 DN50 external thread |
| Surface characteristics Ra/Rz of the wetted parts | 1.25 μ m |
| Display Unit | L/min; l/h; m³/h; m/s |