Display | Five digits (-9999 to 99999) 0.70″ (17.8 mm) high, 7-segment, automatic lead zero blanking |
Decimal Point | Upper process display has up to four decimal places or none: d.dddd d.ddd, d.dd, d.d, or ddddd |
Display Update Rate | - Ambient > -25°C: 2 Updates/Second
- Ambient < -25°C: 1 Update/5 Seconds
|
Externally Powered Backlight | Voltage Range: 9-36 VDC |
Display Orientation | The display may be mounted at 90° increments up to 270° from the default orientation |
Over Range | Display flashes 99999 |
Under Range | Display flashes -9999 |
Programming Method | Four SafeTouch®through-glass buttons when the cover is installed. Four internal pushbuttons when the cover is removed. |
Noise Filter | Programmable - Lo, Med, Hi, or Off |
Recalibration | Recalibration is recommended at least every 12 months. |
Max./Min. Display | Max/Min readings reached by the process are stored until reset by the user or until power to the meter is turned off. |
Password | Programmable password restricts modification of programmed settings |
Advanced Functions | Live input calibration, linearization, square root, or programmable exponent. |
Alarm Indication | Flashing display plus HI/LO indicators |
Non-Volatile Memory | All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost. |
Normal Mode Rejection | 64 dB at 50/60 Hz |
Operating Temperature Range | -40 °C to 75 °C |
Storage Temperature Range | -40 °C to 75 °C |
Relative Humidity | 0 to 90% non-condensing |
Connections | Screw terminals accept 12 to 22 AWG wire |
Enclosure | Explosion-proof die-cast aluminum with glass window, corrosion-resistant epoxy coating |
Mounting | May be mounted directly to the conduit. Two slotted flanges for wall mounting or NPS 1-1/2" to 2-1/2" or DN 40 to 65 mm pipe mounting. |
Overall Dimensions | 5.65″ x 5.25″ x 4.86″ (W x H x D) |
Weight | 5.00 lbs (80 oz, 2.27 kg) |