Welcome to the New PrimeBuy.com We've upgraded our store to make finding and ordering the equipment you need faster and easier. Returning customers: your account and order history have moved to the new site. To sign in for the first time, please set a new password using “” on the sign-in page. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed. Thank you for choosing PrimeBuy

Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
IFM
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs
Calorimetric Flow Sensor with 45mm Probe and 1 Outputs

IFM SA5020 Calorimetric Flow Sensor with 45mm Probe and 1 Outputs

Brand: IFM
Part #:
SA5020
Model #:
SAD10XDBFRKG/US-100
Condition:
Brand New

Choose Number of Outputs

Choose Probe Length (mm)

$527.00 /Each
Typically In Stock
Check availability
$527.00 /Each
Manufacturer warranty

Description

$527.00 /Each
Typically In Stock
Check availability

Technical details

Main features
  • Number of Outputs 1
  • Material Stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PBT-GF20; PBT-GF30
  • Accuracy ± (10 % MW + 2 % MEW); (reference conditions: DN50; Inside diameter 51 mm; within the range of maximum sensitivity: 20 ° C /<6 bar; Insertion depth: 15 mm; inlet pipe length: 2.5 m; standard velocity to DIN ISO 2533 at the sensor tip)
  • System Gold-plated contacts
  • Output Signal Switching signal; analog signal; frequency signal; IO-Link; (configurable)
  • Communication Interface IO-Link
  • Protection Class III
  • Number of Digital Outputs 2
  • Installation Recommended for pipe diameters; ( 15 - 51 mm)
  • Process Connection Threaded connection M18 x 1,5 Internal thread
  • Output Function Normally open / closed; (configurable)
  • Probe Length (mm) 45
  • Electrical Design PNP/NPN
  • Operating Mode Relative; absolutely gaseous; (absolute: reference measurement recommended; Factory Setting: relative)
  • Protection IP 65 IP 67
  • Connection Connector: 1 x M12; coding: A; Contacts: gold-plated
  • Overload Protection Yes
  • Repeatability ± (3 % MW + 0,6 % MEW)
  • Short-circuit protection Yes
  • Operating voltage [V] 18 - 30 DC; (to SELV/PELV)
  • Media Air
  • Temperature Drift ± 0,005 K/° C
  • Reverse Polarity Protection Yes
  • Current Consumption [mA] < 100
  • Analog Current Output [mA] 4 - 20; (scalable)
  • Maximum Load [Ω ] 350
  • Ambient Temperature [° C] -40 - 80
  • Storage Temperature [° C] -40 - 100
  • MTTF [Years] 131
  • Weight [g] 309.1
  • Medium Temperature [° C] -20 - 90
  • Total Number of Outputs 2
  • Number of Analog Outputs 1
  • Materials (Wetted Parts) Stainless steel (1.4404 / 316L); Gasket: FKM
  • Maximum Voltage Drop Switching Output DC [V] 2.5
  • Power-on Delay Time [s] 10
  • Response Time [s] 7
  • Pressure Rating [bar] 100
  • Pressure Rating [MPa] 10
  • Permanent Current Rating of Switching Output DC [mA] 250
  • MAWP (for Applications According to CRN) [bar] 100
  • Frequency of the output [Hz] 0 - 1000
  • Frequency at the end point FRP [Hz] 100 - 1000
  • Measuring Range [° C] -20 - 90
  • Resolution [° C] 0.2
  • Accuracy [K] ± 2 / + 8; (flow velocity>20 % VMR and 20 ° C: ± 2)
  • Dynamic Response T05 / T09 [s] 30 (T09); (Flow velocity: ≥ 10 m/s)
  • Parameter Setting Hysteresis / window; normally open / closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value color
  • Transmission Type COM2 (38,4 kBaud)
  • IO-Link Revision 1.1
  • SDCI Standard IEC 61131-9
  • Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
  • SIO Mode Yes
  • Required Master Port Class A
  • Process Data Analog 2
  • Process Data Binary 2
  • Minimum Process Cycle Time [ms] 3
  • Type of Short-Circuit Protection Yes (non-latching)
  • Probe Length L [mm] 45
  • Setting Range [m/s] 0 - 30, 0 - 60
  • Greatest Sensitivity [m/s] 0.6 - 30
  • Display range [m/s] 0 - 36
  • Resolution [m/s] 0.2
  • Set point SP [m/s] 2 - 30
  • Reset point rP [m/s] 0.6 - 28.6
  • Analog start point ASP [m/s] 0 - 24
  • Analog end point AEP [m/s] 6 - 30
  • Frequency end point, FEP [m/s] 6.6 - 30