Welcome to the New PrimeBuy.comWe've upgraded our store to make finding and ordering the equipment you need faster and easier. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed.Thank you for choosing PrimeBuy
ProfilesSmart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO ModeYes
Required Master Port ClassA
Process Data Analog1
Process Data Binary2
Minimum Process Cycle Time [ms]2.3
Type of Short-Circuit ProtectionYes (non-latching)
Min. bursting pressure [MPa]120
Measuring ElementDiaphragm seal
Vacuum Resistance [mbar]-1000
Hysteresis Deviation [% of the Span]< ± 0,1; (Turn down 1: 1)
Measuring range [MPa]0 - 60
Integrated WatchdogYes
Switching Frequency DC [Hz]< 500
Set point SP [MPa]0.4 - 60
Reset point rP [MPa]0.1 - 59.7
Analog start point [MPa]0 - 48
Analog end point [MPa]12 - 60
In steps of [MPa]0.1
Switch Point Accuracy [% of the Span]< ± 0,4; (Turn down 1: 1)
Response Time [ms]< 1.5
Delay Time Programmable dS, dr [s]0 - 50
Maximum Response Time Analog Output [ms]3