Welcome to the New PrimeBuy.com We've upgraded our store to make finding and ordering the equipment you need faster and easier. Returning customers: your account and order history have moved to the new site. To sign in for the first time, please set a new password using “” on the sign-in page. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed. Thank you for choosing PrimeBuy

Det-Tronics
PIRECLA3A1B2 PointWatch 3/4" NPT Gas Detector

Det-Tronics 011904-020 PIRECLA3A1B2 PointWatch 3/4" NPT Gas Detector

Part #:
011904-020
Condition:
Brand New
$5,553.00 /Each
$5,868.20 You save $315.20 5%
Free shipping
$5,553.00 /Each
$5,868.20 You save $315.20 5%
Manufacturer warranty

Description

$5,553.00 /Each
$5,868.20 You save $315.20 5%
Free shipping

Technical details

Main features
  • Model PIRECLA3A1B2
  • Approvals INMETRO (Brazil)
  • Input Voltage 24 Vdc nominal. Operating range is 18 to 32 Vdc Ripple cannot exceed 0.5 volt P-P
  • Accuracy ±3% from 0 to 50% LFL, ±5% from 51 to 100% LFL
  • Output 4-20 mA with HART Protocol RS-485: CO2 0-2%/vol Full Scale Range
  • Classification Division/Zone Ex d
  • Power Consumption 4.0 watts nominal at 24 Vdc 7.5 watts maximum at 24 Vdc 10 watts maximum at 32 Vdc
  • Temperature Range Operating: -55°C to +75°C (-67°F to +167°F) Storage: -55°C to +85°C (-67°F to +185°F)
  • Humidity 0 to 99% R.H. (Det-Tronics verified) 5 to 95% R.H. (FM/CSA/DEMKO verified)
  • Detection Range 0 to 100% LFL standard (other ranges are configurable)
  • Current output Linear 4-20 mA (current source/sink, isolated/non-isolated
  • Relays No
  • Short circuit current Isc: 5.4 amperes Isc (fuse): 3.1 amperes Power Supply Max Voltage: Um = 250V
  • Warmup Time Two minutes from cold power-up to normal mode; 1 hour minimum recommended.
  • HART Port Yes
  • Relays (Opt.) rated at 600 ohms maximum loop resistance at 24 Vdc operating voltage.
  • Detectable Gases Most flammable hydrocarbon vapors are detectable. Eclipse is performance certified to methane, propane, ethylene, and butane, and is shipped from the factory set and calibrated to one of these gases. For the detection of other gases, a configuration using HART, MODBUS, or EQP system software, and device calibration are required
  • Device Configuration Configuration parameters include tag number, measurement range, signal processing algorithm, alarm levels, and other selectable parameters.
  • Alarm Setpoint Range Low Alarm: 5 to 60% LFL High Alarm: 5 to 60% LFL. Note: Low alarm range for EQP model is 5-40% LF