Welcome to the New PrimeBuy.com We've upgraded our store to make finding and ordering the equipment you need faster and easier. Returning customers: your account and order history have moved to the new site. To sign in for the first time, please set a new password using “” on the sign-in page. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed. Thank you for choosing PrimeBuy

SurgeX
Bestseller
Programmable Sequencer Surge Eliminator, 8 Outlets

SurgeX SEQ-1U Programmable Sequencer Surge Eliminator, 8 Outlets

Brand: SurgeX
Part #:
SEQ-1U
Condition:
Brand New
Not for Export

Choose Outlet Configuration

$1,330.00 /Each
$1,349.00 You save $19.00 1%
Free shipping
Typically In Stock
Check availability
$1,330.00 /Each
$1,349.00 You save $19.00 1%

Notification

This product is prohibited for export and is subject to export control laws and regulations of the U.S. Government. Please review our Export Policy.

Manufacturer warranty

Description

$1,330.00 /Each
$1,349.00 You save $19.00 1%
Free shipping
Typically In Stock
Check availability

Technical details

Main features
  • Weight 13 lbs (5.9 kg)
  • Dimensions 1.75" H x 19.0" W x 12.25" D (4.4 x 48.3 x 31.0 cm)
  • Load Rating 20 amps at 120 volts
  • Outlet Configuration 8 Outlets
  • Temperature Range 5° to 35° C
  • Agency Listings UL 1449 3rd Edition, UL 1283 5th Edition, CSA C22.2 No.8-M1986 (R2008)
  • Humidity Range 5% to 95% R.H., non-condensing
  • Control Inputs Momentary Switch, Latching Switch, Contact Closure or 5-30 Vdc
  • UL 1449 Adjunct Classification Test Results 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts; no failures
  • Federal Guidelines Grade A, Class 1, Mode 1 (CID A-A-55818)
  • EMI/RFI Filter, Normal Mode (50-ohm load) > 30 dB 100 KHz - 50 MHz
  • EMI/RFI Filter, Common Mode (50-ohm load) > 20 dB 1 MHz - 50 MHz
  • Maximum Applied Surge Voltage 6000 volts
  • Endurance (C62.41-1991 Category B3 pulses) 1 kV > 500,000; 3 kV > 10,000; 6 kV > 1000
  • Auxiliary Relay Contact Rating 30V DC at 1A
  • Surge Let-Through Voltage (6000-volt surge) 0 Volts
  • Under-Voltage Auto Shutdown Adjustable from 90V to 110V
  • Over-Voltage Auto Shutdown Adjustable from 130V to 150V
  • Maximum Load Inrush Energy 1400 Joules total during power-up
  • Input Control Current 3 mA
  • DC Voltage Output 12 Vdc, 40 mA maximum load
  • Contact Closure Max Resistance 40 mA
  • 12V DC Output Max Current 100 Ω
  • Delay Times 1 - 40 seconds in 1 second increments