| Reference Conditions for Accuracy |
| Reference Temperature | 23°C +/- 2°C |
| Input Waveform | Sinusoidal (distortion factor 0.005) |
| Input Frequency | 50 or 60 Hz ±2% |
| Auxiliary Supply Voltage | Rated Value ±1% |
| Auxiliary Supply Frequency | Rated Value ±1% |
| Accuracy |
| Voltage | ±1% of range (20 - 100% of Nominal value) |
| Current | ±1% of range (10 - 100% of Nominal value) |
| Frequency | 0.5% of mid-frequency |
| Input Voltage |
| Nominal Input Voltage (AC RMS) | Phase -Neutral 290V L-N, Line-Line 500V L-L |
| Max Continuous Input Voltage | 120% of the rated value |
| Nominal Input Voltage Burden | < 0.3 VA approx. per phase (For external auxiliary meter) |
| System PT Secondary Values | 100VLL to 500VLL programmable on-site. |
| System PT Primary Values | 100VLL to 692kVLL programmable on-site. |
| Input Current |
| Nominal Input Current | 5A AC RMS |
| System CT Secondary Values | 1A & 5A programmable on site |
| System CT Primary Values | From 1A up to 9999A (for 1 or 5 Amp ) |
| Max Continuous Input Current | 120% of the rated value |
| Nominal Input Current Burden | < 0.2 VA approx. per phase |
| Auxiliary Supply |
| External Aux | 40 V - 300V AC-DC (± 5 % ) |
| Self-Powered | Input voltage range from 80% to 100% of the Rated value. |
| Frequency Range | 45 to 65 Hz |
| VA Burden | 3 VA Approx. |
| Overload Withstand |
| Voltage | 2 x rated value for 1 second, repeated 10 times at 10-second intervals |
| Current | 20x rated value for 1 second, repeated 5 times at 5 min intervals |
| Operating Measuring Ranges |
| Voltage Range With External Aux | 10 - 120% of the rated value |
| Voltage Range With Self Power | 80 - 120% of the rated value |
| Current Range | 10 - 120% of the rated value |
| Frequency | 45 - 65 Hz |
| Environmental |
| Operating Temperature | -20° to +70°C |
| Storage Temperature | -30°C to +80°C |
| Relative Humidity | 0 to 95% non condensing |
| Warm-Up Time | Minimum 3 minute |
| Shock | 15g in 3 planes |
| Vibration | 10.. - 55 Hz, 0.15mm amplitude |
| Safety |
| EMC Compatibility | Compliance with International standard IEC 61326. |
| Interference Emission | IEC 61326-1 2005, Class, A |
| Interference Immunity | IEC 61326-1 2005 |
| Electrostatic Discharge | IEC 61000-4-2 - 4kV/8kV contact/air. (ESD) |
| EM Field | IEC 61000-4-3 - 10 V/m (80 MHz to 1 GHz), 3 V/m (1.4 Ghz to 2 GHz), 1 V/m (2 GHz to 2.7 GHz) |
| Burst | IEC 61000-4-4 -- 2 kV (5/50 ns, 5 kHz) |
| Surge | IEC 61000-4-5 -- 1 kVLL / 2 kVLN |
| Conducted RF | IEC 61000-4-5 - 3 V (150 kHz to 80 MHZ) |