Welcome to the New PrimeBuy.com We've upgraded our store to make finding and ordering the equipment you need faster and easier. Returning customers: your account and order history have moved to the new site. To sign in for the first time, please set a new password using “” on the sign-in page. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed. Thank you for choosing PrimeBuy

Three-Phase Power Meter, 1000 A
Three-Phase Power Meter, 1000 A
PCE Instruments
Three-Phase Power Meter, 1000 A
Three-Phase Power Meter, 1000 A

PCE Instruments PCE-830-2 Three-Phase Power Meter, 1000 A

Part #:
PCE-830-2
Condition:
Brand New
$2,989.00 /Kit
$4,050.00 You save $1,061.00 26%
Free shipping
Typically In Stock
Check availability
$2,989.00 /Kit
$4,050.00 You save $1,061.00 26%
Manufacturer warranty

Description

$2,989.00 /Kit
$4,050.00 You save $1,061.00 26%
Free shipping
Typically In Stock
Check availability

Technical details

Main features
  • Power 8 AA batteries (Mignon)
  • Weight 1.16 kg / 2.56 lbs
  • Dimensions 257 mm x 155 mm x 57 mm 10.1 in x 6.10 in x 2.24 in
  • Package Included Power Meter with PCE-6802 Amp Clamp
  • Display Backlit LCD with dot-matrix
  • Memory 512 kB for a maximum 52,420 readings taken by 1 phase / 2 conductors
  • Port USB
  • Total Harmonic Distortion 0.0 to 20.0% / 0.1% / ±2% 20.0% to 100% / 0.1% / ±6% of reading ±1% 100% to 999.9% / 0.1% / ±10% of reading ±1%
  • Operating Conditions max. 85% relative humidity -10° C to 50° C / 14° F to 122° F
  • Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1) 5.0 W to 999.9 W / 0.1 W / ±1% ±0.8 W 1.000 kW to 9.999 kW / 0.001 kW / ±1% ±8 W 10.00 kW to 99.99 kW / 0.01 kW / ±1% ±80 W 100.0 kW to 999.9 kW / 0.1 kW / ±1% ±0.8 kW 1000 kW to 9999 kW / 1 kW / ±1% ±8 kW 0.000 MW to 9.999 MW / 0.001 MW / ±1% ±80 kW
  • Current AC (50 Hz or 60 Hz, Auto Range Select, TRMS) 10.00 A / 0.01 A / 4 A to 100.0 A / 0.01 A / ±0.5% ±0.5 A 40 A to 1000.0 A / 0.1 A / ±0.5% ±5 A
  • Voltage AC (50 Hz or 60 Hz, TRMS) 20.0 V - 500.0 V / 0.1 V / ±0.5 % ±5 digits (grounded) 20.0 V - 600.0 V / 0.1 V / ±0.5 % ±5 digits (phase to phase)
  • Harmonic distortionof AC Voltage 1° to 20° / 0.1% / ±1.0% 21° to 49° / 0.1% / 4% of reading ±2.0% 50° to 99° / 0.1% / 6% of reading ±2.0%
  • Harmonics of AC Current in % 1° to 10° / 0.1% / ±2% 21° to 49° / 0.1% / 4% of reading ±2.0% 50° to 99° / 0.1% / 6% of reading ±2.0%
  • Power Factor (PF) 0.00 to 1.00 / 0.01 / ±0.04
  • Phase Angle (Phi) -180° to 180° / 0.1° / ±1°
  • Maximum Measurement of AC Voltage and Current 50 Hz / 19 µS / ±5% ±30 digits 60 Hz / 16 µS / ±5% ±30 digits
  • Peak Value Measurement of AC Voltage and Current 1.00 to 99.99 / 0.01 / ±5% ±30 digits
  • The Frequency Range in Automatic Mode 45 Hz to 65 Hz / 0.1 H z / 0.1 Hz
  • Software and Cable Yes, for Windows 2000, XP, ME
  • Type of Protection / Standards IEC 61010, 600 V/CAT III