Welcome to the New PrimeBuy.com We've upgraded our store to make finding and ordering the equipment you need faster and easier. Returning customers: your account and order history have moved to the new site. To sign in for the first time, please set a new password using “” on the sign-in page. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed. Thank you for choosing PrimeBuy

Moxa
40W/1.7A DIN-Rail 24V VDC Power Supply

Moxa MDR-40-24 40W/1.7A DIN-Rail 24V VDC Power Supply

Brand: Moxa
Part #:
MDR-40-24
Condition:
Brand New
$141.10 /Each
Typically In Stock
Check availability
$141.10 /Each
Manufacturer warranty

Description

$141.10 /Each
Typically In Stock
Check availability

Technical details

Main features
  • Current Rating 0 to 1.7 A
  • Weight 260 g (0.57 lb)
  • Dimensions 40 x 90 x 100 mm (1.57 x 3.54 x 3.94 in)
  • Voltage 24 VDC
  • Wattage 40 W
  • Voltage Range 85 to 264 VAC (47 to 63 Hz) 120 to 370 VDC
  • Protection Type Constant current limiting recovers automatically after the fault condition is removed, Shut down the operating voltage, and repower on to recover
  • Operating Temperature -20 to 70°C (-4 to 158°F)
  • EMC EN 55032/35 EN 61000-3-2 Class A EN 61000-3-3 EN IEC 61204-3 EN IEC 61000-6-2
  • Safety UL 508 EN 62368-1 IEC 62368-1
  • Rated Output Power 105 to 150%
  • EMS IEC 61000-4-2 ESD: Contact: 6 kV Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV Signal: 2 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
  • Ambient Relative Humidity 20 to 90% (non-condensing)
  • Ripple and Noise 150 mVp-p
  • Voltage Adjustment Range 24 to 30 VDC
  • Setup/Rise Time at Full Load 500 ms, 30 ms at 115 VAC 500 ms, 30 ms at 230 VAC
  • Typical Efficiency 88%
  • Typical Current 0.7 A at 230 VAC, 1.1 A at 115 VAC
  • Overvoltage Range 31.2 to 36 V
  • Maximum Operating Temperature at Full Load 60°C
  • Typical Hold-Up Time at Full Load 20 ms at 115 VAC 50 ms at 230 VAC
  • Typical Current (cold start) 60 A at 230 VAC, 30 A at 115 VAC

Related items.

Customers buy together with this.

Reviews.

There are currently no reviews for this product. You can leave the first review and share your experience.

Your history.