| Humidity Measurement Range | 0 to 100% RH (non-condensing) |
| Accuracy | ± 2% RH (0 to 80%), ± 3% RH (80% to 100%) |
| Resolution | 0.01 %RH |
| Response time - Leaded sensor | 40 seconds (8-second time constant) |
| Response time - Non-leaded sensor | 6+ hours (75-minute time constant) |
| Temperature Measurement Range - Leaded sensor | -25°C to 70°C (-13°F to 158°F) |
| Temperature Measurement Range - Non-leaded sensor | - - ALTA Commercial: 10°C to 50°C (50°F to 122°F)
- - ALTA Enterprise: -18°C to 55°C (0°F to 130°F) using alkaline batteries
- - ALTA Industrial: -40°C to 70°C (-40°F to 158°F)
|
| Accuracy | ± 0.3°C (0.54°F) Typical |
| Resolution | 0.01°C (0.018°F rounded to 0.01 decimal place) |
| Response time - Leaded sensor | 15 seconds (3 second time constant) |
| Response time - Non-leaded sensor | 100 minutes (20 minute time constant) |
| Leaded Probe Tip dimensions | 11 mm Wide x 4.5 mm Tall (0.44" Wide x 0.16" Tall) |
| Tip construction | PCA with high accuracy digital temp/humidity sensing element, soldered interface wires, all wrapped in waterproof heat shrink with small hole for air exchange. |
| Wire details | 4-conductor, 26 AWG, stranded copper |
| Insulation | PVC, 0.010" |
| Shield | No |
| Jacket | PVC (black) |
| Overall Diameter | 4.25 ± 0.2 mm (0.17" ± 0.007) |
| Ratings / Approvals | UL AWM STYLE 2464, cUL AWM I/II A 80°C 300V FT1 LF |
| Temperature Rating | -25°C to 80°C (-13°F to 176°F) |
| Voltage Rating | 300 V Max |
| Dielectric Strength | 1500 V RMS |
| Cable length | Standard: 0.9 m (3 ft), Optional: 0.1, 3, 7.5 m (0.33, 10, 25 ft) |
| Wireless Data logging | Sensor logs 2000 to 4000 readings if gateway connection is lost (non-volatile flash, persists through power cycling): 10-minute Heartbeats = ~22 days, 2-hour Heartbeats = ~266 days |
| Wireless protocol | ALTA Proprietary Frequency-Hopping Spread Spectrum (FHSS) |
| Wireless transmission power (EIRP) | 50 mW (900MHz), 25 mW (868 MHz), 10 mW (433 MHz) |
| Wireless range | 2,000+ ft. through 18+ walls with the ALTA XL Gateway |
| Security | Encrypt-RF (256-bit key exchange and AES-128 CTR) |
| Battery voltage range | 2.0 to 3.8 VDC |
| Operating altitude (non-pressurized environments) | -15.2 to 1,982 m (-50 to 6,500 ft) |
| Storage altitude (non-pressurized environments) | -15.2 to 3,048 m (-50 to 10,000 ft) |
| Operating humidity | 5 to 85% RH (non-condensing) |
| Battery | 1x 3.6V AA Lithium Thionyl Chloride, 1500mAh, pre-installed |
| Battery Life | 10+ years expected |
| Operating Temperature Range (non-leaded measurement range) | -40°C to 70°C (-40°F to 158°F) |
| Wireless Antenna Type | 1/2-wave waterproof dipole with RP-SMA connector and swivel neck; dBi of 3.0 (900/868MHz) or 2.5 (433 MHz); length of 8.27" (210mm) (900/868MHz) or 7.68" (195mm) (433 MHz); diameter at thickest point of 0.55" (14mm) |
| Weight | 4.7 oz. (133 g) with 0.13 m (5.0") lead; 5.2 oz. (147 g) with 0.9 m (3.0') lead |
| Enclosure Rating | IP-65 (dust-proof and waterproof but not submersible); NEMA 1, 2, 4, 4x, 12, and 13 rated, sealed, and weatherproof |
| UL Rating | UL Listed to UL508-4x specifications (File E194432) |