| Product Characteristics |
| Number of Inputs and Outputs | Number of Digital Outputs: 2 |
| Process Connection | Threaded connection Rc 3/4 Internal thread DN20 |
| System | Gold-plated contacts |
| Media | Water; glycol solutions; Coolants |
| Medium Temperature [° C] | -10 - 90 |
| Pressure Rating [bar] | 12 |
| Pressure Rating [MPa] | 1.2 |
|
| Electrical Data |
| Operating Voltage [V] | 18 - 30 DC |
| Current Consumption [mA] | < 30 |
| Minimum Insulation Resistance [MΩ ] | 100; (500 V DC) |
| Protection Class | III |
| Reverse Polarity Protection | Yes |
| Power-on Delay Time [s] | < 3 |
| Inputs / Outputs |
| Number of Inputs and Outputs | Number of Digital Outputs: 2 |
| Outputs |
| Total Number of Outputs | 2 |
| Output Signal | Switching signal; frequency signal; IO-Link; (configurable) |
| Electrical Design | PNP/NPN |
| Number of Digital Outputs | 2 |
| Output Function | Normally open / closed; (configurable) |
| Maximum Voltage Drop Switching Output DC [V] | 2.5 |
| Permanent Current Rating of Switching Output DC [mA] | 100 |
| Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Measuring/Setting Range |
| Frequency at the end point FRP [Hz] | 100 - 1000 |
| Measuring dynamics | 1: 20 |
| Temperature Monitoring |
| Measuring Range [° C] | -10 - 90 |
| Display range [° C] | -30 - 110 |
| Resolution [° C] | 0.5 |
| Set point SP [° C] | -9 - 90 |
| Reset point rP [° C] | -10 - 89 |
| In Steps of [° C] | 0.5 |
| Frequency start point, FSP [° C] | -10 - 70 |
| Frequency end point, FEP [° C] | 10 - 90 |
| Frequency at the end point FRP [Hz] | 100 - 1000 |
| Accuracy / deviations Flow monitoring |
| Accuracy (in the Measuring Range) | ± 2 % MEW; (water) |
| Repeatability | ± 0,5 % MEW |
| Temperature Monitoring |
| Accuracy [K] | ± 1 |
| Reaction Times Flow monitoring |
| Response Time [s] | 1; (dAP = 0) |
| Damping Process Value dAP [s] | 0 - 5 |
| Temperature Monitoring |
| Dynamic Response T05 / T09 [s] | T09 = 6 |
| Software / Programming |
| Parameter Setting | Hysteresis / window; normally open / closed; switching logic; Frequency output; switch-on/switch-off delay; Damping; Display Unit |
| Interfaces |
| Communication Interface | IO-Link |
| Transmission Type | COM2 (38,4 kBaud) |
| IO-Link Revision | 1.1 |
| SDCI Standard | IEC 61131-9 |
| Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO Mode | Yes |
| Required Master Port Class | A |
| Process Data Analog | 2 |
| Process Data Binary | 2 |
| Minimum Process Cycle Time [ms] | 3 |
| Operating Conditions |
| Ambient Temperature [° C] | 0 - 60 |
| Storage Temperature [° C] | -20 - 80 |
| Protection | |
| MTTF [Years] | 342 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Mechanical Data |
| Weight [g] | 487.5 |
| Material | Stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U |
| Materials (Wetted Parts) | Stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM |
| Tightening Torque [Nm] | 30 |
| Process Connection | Threaded connection Rc 3/4 Internal thread DN20 |
| Electrical Connection |
| Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |