Welcome to the New PrimeBuy.comWe've upgraded our store to make finding and ordering the equipment you need faster and easier. If anything gets in the way of your order, or you notice something that isn't working as it should, let us know through live chat or email. A member of our team will help you and make sure it gets fixed.Thank you for choosing PrimeBuy
Maximum Relative Air Humidity [%]95; (IEC 60068-2-30)
Weight [g]2044.5
Dimensions [mm]124 x 126 x 132.6
Frequency AC [Hz]47 - 64
Operating Voltage Tolerance [%]15 - 10
Short-circuit proofYes
Ambient Temperature [°C]-25 - 70
Storage Temperature [°C]-40 - 85
Degree of Soiling2; (IEC 62103: conductive soiling not permitted)
Nominal Voltage AC [V]<230
Input Voltage Range AC [V]100 - 240
Output Voltage DC [V]24 - 28
Output Voltage [V]Adjustable; Output Voltage to SELV, PELV
Maximum Output Current at Minimum Output Voltage [A]40
Maximum Output Current at Maximum Output Voltage [A]34.3
Maximum Output Current Peak at Minimum Output Voltage [A]60
Maximum Output Current Peak at Maximum Output Voltage [A]51.5
Output Power (Permanent) [W]960
Output Power (Peak) [W]1440
Power Factor (Nominal Voltage 120 V AC / 60 Hz)0.99
Power Factor (Nominal Voltage 230 V AC / 50 Hz)0.99
Power Reserve [%]50
Number of Output Circuits1
Maximum Residual Ripple [mV]100
Switch-on Peak Current (Nominal Voltage 120 V AC / 60 Hz) [A]17
Switch-on Peak Current (Nominal Voltage 230 V AC / 50 Hz) [A]11
Inrush Current limitationYes
Efficiency (Nominal Voltage 120 V AC / 60 Hz) [%]93.6
Efficiency (Nominal Voltage 230 V AC / 50 Hz) [%]94.6
External Input Protection≥ B-16 A / ≥ C-16 A
Derating [W/K]24 (60 - 70 °C)
Mains Buffering Time (Nominal Voltage 120 V AC / 60 Hz) [ms]27
Mains Buffering Time (Nominal Voltage 230 V AC / 50 Hz) [ms]27
Input Current (Nominal Voltage 120 V AC / 60 Hz) [A]8.6
Input Current (Nominal Voltage 230 V AC / 50 Hz) [A]4.5
Power Loss (Nominal Voltage 120 V AC / 60 Hz) [W]65.6
Power Loss (Nominal Voltage 230 V AC / 50 Hz) [W]54.8
Back Feeding Protection [V]35
Overload PerformanceHiccup Mode; in the event of overload / short circuit, the output alternately supplies continuous power for 2 s and then switches off for 17 s
Type DC-OK signalRelay output
Reliability of the DC OK signal60 V DC (0.3 A) / 30 V DC (1 A) / 30 V AC (0.5 A)
Power Factor Correction (PFC)Met