Daisy-Chain Function | Voltage Supply; fieldbus interface |
Electrical Data |
Operating Voltage [V] | 20 - 30 DC; (US; to SELV/PELV) |
Current Consumption [mA] | 300 - 3900; (US) |
Protection Class | III |
Additional Voltage Supply [V] | 20 - 30 DC; (UA) |
Actuator Supply UA |
Maximum Current Load Total [A] | 8 |
Current Rating per Port [A] | 2; (adjustable: 0 - 2; Factory setting: 2) |
Sensor Supply US |
Maximum Current Load Total [A] | 3.6 |
Current Rating per Port [A] | 2; (adjustable: 0 - 2; Factory setting: 0,45) |
Inputs / Outputs |
Total Number of Inputs and Outputs | 16; (configurable) |
Number of Inputs and Outputs | - Number of Digital Inputs: 12
- Number of Digital Outputs: 12
|
Inputs |
Number of Digital Inputs | 12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1) |
Switching Level High [V] | 11 - 30 |
Switching Level Low [V] | 0 - 5 |
Digital Inputs Protected Against Short Circuits | Yes |
Outputs |
Number of Digital Outputs | 12; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 2) |
Short-Circuit Proof | Yes |
Actuator Supply UA |
Maximum Current Load per Output [mA] | 2000 |
Sensor Supply US |
Maximum Current Load per Output [mA] | 2000 |
Interfaces |
Communication Interface | Ethernet; IO-Link |
Ethernet - ProfiNet |
Transmission Standard | 100Base-TX |
Transmission Rate | 100 MBit/s |
Protocol | ProfiNet |
IO-Link Master |
Transmission Type | - COM1 (4,8 kBaud)
- COM2 (38,4 kBaud)
- COM3 (230,4 kBaud)
|
IO-Link Revision | 1.1 |
Number of Ports Class A | 4 |
Number of ports class B | 4 |
Operating Conditions |
Ambient Temperature [°C] | -25 - 60 |
Storage Temperature [°C] | -25 - 85 |
Maximum Relative Air Humidity [%] | 90 |
Protection | |
Protection Rating (NEMA 250) | 6P |
Degree of Soiling | 2 |
MTTF [years] | 43 |
Mechanical Data |
Weight [g] | 412.1 |
Material | - Housing: PA orange
- Socket: brass nickel-plated
|
Sealing Material | FKM |
Electrical Connection - Ethernet |
IN / OUT XF1, XF2 | Connector: M12; coding: D; sealing: FKM |
Electrical Connection - Process Connection |
IO-Link Port Class B X1 - X4 | Connector: M12; coding: A; sealing: FKM |
Electrical Connection - Voltage Supply IN |
XD1 | Connector: M12; coding: L |
Electrical Connection - Voltage Supply OUT |
XD2 | Connector: M12; coding: L; sealing: FKM |