| Power Input | 11-26VAC/VDC |
| Signal Input | Universal Input T/C, RTD, mV (0-60mV) |
| Output 1 | SSR drive 5 VDC, 30 mA |
| Output 2 | None |
| Communications | None |
| Protective Class | IP50 Standard |
| General |
| Power | 90-250 VAC, 47-63Hz, 10VA, 5W Maximum |
| Input Thermocouple | Type J, K, T, E, B, R, S, N, L, C and P |
| Input RTD | PT 100 ohm DIN and PT 100 JIS |
| Input Linear | 4-20mA, 0-20mA, 0-60mV, 0-1, 0-5, and 0-10VDC |
| Accuracy | Typically better than +/- 0.25% |
| Sensor Break | 4 seconds for T/C and RTD inputs, 0.1 second for linear mA and VDC inputs |
| Common Mode Rejection | 120dB |
| Sample Rate | 5 times per second |
| Remote Reset | Standard |
| Limit Output Types |
| Relay | Form C 2.0 Amp/240VAC |
| SSR Drive | 5 VDC, 30mA, 14 VDC, 40mA |
| Triac | 1.0 Amp/240VAC |
| Dual LED 4 Digit Display | Process 0.56" and Setpoint 0.4" |
| Display Logic | Upper Display: Process (temperature) is always shown, Lower Display: Configurable, non-Alarm condition display SAFE or Setpoint value, when in alarm Setpoint is shown |
| Status Indicator | Output #1, Output #2, °F, °C, Lock |
| Environmental and Physical |
| Operating Temperature | -10 to 50°C |
| Storage Temperature | -40 to 60°C |
| Humidity | 0-90% RH (non-condensing) |
| Insulation | 20M ohms Minimum (500VDC) |
| Dielectric Strength | 2000 VAC, 50/60 Hz, 1 minute |
| Vibration Resistance | 10-55 Hz, 10 m/s for 2 hours |
| Shock Resistance | 200m/s (20g) |
| Molding | Flame retardant polycarbonate |
| Dimension | 3.77" (H) x 3.77" (W) x 2.08" (D) |
| Weight | 8.84 oz (250g) |