| Power | |
| Input Voltage Range | 90 to 264 VAC |
| Input Current, Max (115 / 230 VAC) | 5.0 A / 2.5 A |
| Inrush Current, Typical (115 / 230 VAC) | 20 A / 40 A |
| Output Voltage & Power | 48 to 55 VDC, 480 W |
| Summary Fault Relay (48 VDC Models Only) | Form A (normally open relay), closed when DC 48 to 56 V is being produced |
| Environmental | |
| Operating Temperature | -30 °C to +70 °C |
| Storage Temperature | -40 °C to +80 °C |
| Relative Humidity - Operating | 20% to 95%, non-condensing |
| Relative Humidity - Storage | 10% to 95%, non-condensing |
| Cooling | Convection cooled - user should provide sufficient space for passive airflow |
| MTBF | > 100,000 hours |
| Mechanical | |
| Power Input Terminal | Screw terminal, AWG 18 to 14 |
| Power Output Terminal | Screw terminal, AWG 18 to 14 |
| Summary Fault Relay Terminal | Screw terminal, AWG 24 to 16 (48 VDC models only) |
| Weight | 2.2 lb (980 g) |
| General | - Output short circuit protection
- Overcurrent protection
- Overvoltage protection
|
| Approvals & EMC Compliance | - UL / cUL UL 508 Listed
- UL 60950-I, UL 1310 Class 2 Power recognized
- ISA 12.12.01 (Class I, Div 2, Groups A, B, C, & D)
- TUV EN 60950-I, CB scheme
- CE EN 61000-6-3, EN 55022 Class B
- EN 61000-3-2, EN 61000-3-3
- EN 61000-6-2, EN 55024
- EN 61000-4-2 Level 4
- EN 61000-4-3 Level 3
- EN 61000-4-4 Level 4
- EN 61000-4-5 L-N Level 3
- EN 61000-4-6 Level 3
- EN 61000-4-8 Level 4
- EN 61000-4-11
- ENV 50204 Level 2
- EN 61204-3
|
| Vibration | Meets IEC 60068-2-6, Rail Mount: 10-500 Hz, 2G, 60 min for each Axis |
| Shock | Meets IEC 60068-2-27, 15G, 11 ms, 3 Axis, 6 Faces, 3 times for each Face |
| Ordering Information | 48 to 55 VDC, 480 W |