Monitoring | Input power monitoring with Outlet switching. Circuit/Breaker current monitoring.Daisy chain Ethernet connectivity. Local high visibility LED display. |
Input Monitoring | Total Unit Monitoring (kWh, W, VA, PF) Phase (A, B, C) Monitoring (kWh, W, VA, PF, V, A) Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements |
Circuit Monitoring | Circuit / Breaker Monitoring (A) Circuit/Breaker Current Measurements Independently Tested and Verified at 2% Accuracy |
Remote Power Management | Individual Outlet Switching |
VLC Support | Yes |
Quantity Of Inputs | 1 |
Voltage | 200-240/346-415V WYE |
Current | 20A x 3 Phase WYE |
VA per Input (Load Capacity) | 11.0kW (230V) |
Frequency | 50/60Hz |
Over Current Protection | None |
Switch | No |
Scrolling / Rotatable Digital Display | Yes |
Indicators LED(s) | 12 |
Power Cable Wire Gauge | 12/5 |
Power Cable Length | 10ft / 3m |
Power Entry Location | Left Rear |
Plug Type | IEC60309 3P + N + E, 20A, 230/400V, Splashproof IP44 |
Receptacle/Socket Type #1 | Combination C13/C19 |
Quantity on Rear | 12 |
Quantity per Phase | 4 |
Circuit Color ID | 3 Circuit = Orange, Green, Blue |
Style | Banks of 6 |
Voltage per Receptacle/Socket | 230V |
Network Connection | Dual 10/100Mbps Ethernet |
Protocols Supported | DHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog, TACACS+ |
Data Access Formats | CSV datalog, JSON API, JSON datalog |
USB Support | Yes |
IP Reset Button | Yes |
Hard Reboot Button | Yes |
Serial Connection | RS232 via RJ45 |
Remote Sensor RJ Connection Jacks | 1 (Supports up to 16 Sensors) |
Maximum Operating Temperature | 60C / 140F |
Heavy Steel Powder Coat Finish | Black |
Configuration | 19in / 483mm Horizontal Rackmount |
Adjustable Mount Brackets | Yes |
Country of Origin | USA, TAA Compliant |
Chassis Dimensions (HxWxD) | 1.72in x 17in x 12in / 44mm x 432mm x 305mm |