Power supply | 15-35vdc, 20mA max. |
Outputs | 3-wire 0-5V |
Operating Temperature (3) | |
Operating TemperatureCompensated range | - -4 to 175°F (-20-80°C)
- 30 to 158°F (0-70°C)
|
Media Compatibility Transmitter |
Transmitter Only | 316L SS compatible liquids and gases,Viton O-rings |
Media Compatibility Manifold |
Connection | Copper tube, CW614n Brass fittings (2.5-3.5% lead content) |
Manifold O-Rings | Neoprene |
Manifold Valves | Glass filled Acetal (Polyacetal Resin) |
Manifold Material | Anodized Aluminum |
Sensor Performance |
Type | Micro-machined silicon strain gauge |
Accuracy (2) | ±0.25% |
Zero and Spanfrom Factory | Included in ±0.25% accuracy statement |
Temp coefficient zero | - For units<25PSI:±1.7% FS/100°F;±1.5%FS/50°C
- For units >25PSI:±1.1% FS/100°F;±1.0%FS/50°C
|
Temp coefficient span | - For units <25PSI: ±1.7% FS/100°F;±1.5%FS/50°C
- For units >25PSI:±1.1% FS/100°F;±1.0%FS/50°C
|
Line Pressure Effect | Zero Shift ≤0.0035%FS/PSIG line pressure |
Burst Pressure | 500% DP range high side; 300% DP range low side |
Differential Pressure Ranges | 0-50 PSID |
Differntial Overload Pressure | 75 PSID |
Maximum Static/Line Pressure (1) | 250 PSIG |
Accuracy(2) | ±0.125 PSID |
Sensor Performance |
Sensor Enclosure | Laser welded housing, IP65 |
Long Term Stability | ±0.5 %FS/Year |
Shock | 30G |
Vibration | 5G at 50Hz; 10G acceleration |
EMI/RFI Protection | Per CE Requirements |
Connection |
Pressure Connection Transmitter | 1/4" NPT Female |
Pressure Connections Manifold | 1/4" NPT female |
Electrical Connection | DIN43650A |
Environmental | - IP65 (Installed with water-tight fittings)
- 1/2" conduit adapter included
|
Display |
Accuracy | 0.1% |
Output | 4-20mA |
Voltage Drop | <3.5VDC |
Sample Rate | 4/s |
Environmental | IP65 |
Agency |
Transmitter Only | CE, RoHS |
Manifold | CE |
- (1) This is the maximum gauge pressure to maintain 0.25% accuracy.
- (2) FS is defined as the full scale of the selected range. Accuracy includes non-linearity, hysteresis, repeatability, zero, and span tolerance.
- (3) Stated operating range is for electronics only; Media temperature may be considerably higher. Use of devices outside of compensated range may result in drift.
|