Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1) | - 5.0 W to 999.9 W / 0.1 W / ±1% ±0.8 W
- 1.000 kW to 9.999 kW / 0.001 kW / ±1% ±8 W
- 10.00 kW to 99.99 kW / 0.01 kW / ±1% ±80 W
- 100.0 kW to 999.9 kW / 0.1 kW / ±1% ±0.8 kW
- 1,000 kW to 9,999 kW / 1 kW / ±1% ±8 kW
|
Current AC (50 Hz or 60 Hz, Auto Range Select, TRMS) | - 0.04 A to 1 A / 0.001 A / ±0.5% ±0.05 A
- 0.4 A to 10.0 A / 0.01 A / ±0.5% ±0.05 A
- 4 A to 100.0 A / 0.1 A / ±1.0% ±0.5 A
|
Voltage AC (50 Hz or 60 Hz, TRMS) | - 20.0 V - 500.0 V / 0.1 V / ±0.5 % ±5 digits (grounded)
- 20.0 V - 600.0 V / 0.1 V / ±0.5 % ±5 digits (phase to phase)
|
Harmonic distortionof AC Voltage | - 1° to 20° / 0.1% / ±1.0%
- 21° to 49° / 0.1% / 4% of reading ±2.0%
- 50° to 99° / 0.1% / 6% of reading ±2.0%
|
Harmonics of AC Current in % | - 1° to 20° / 0.1% / ±0.2% of reading ±1.0%
- 11° to 20° / 0.1% / ±2% of reading ±1.0%
- 21° to 50° (A)/ 0.1% / ±5% of reading ±1.0%
- 21° to 50° (mA)/ 0.1% / ±10% of reading ±1.0%
- 51° to 99° / 0.1% / ±35% of reading ±1.0%
|
Power Factor (PF) | 0.00 to 1.00 / 0.01 / ±0.04 |
Phase Angle (Phi) | -180° to 180° / 0.1° / ±1° |
Total Harmonic Distortion | - 0.0 to 20.0% / 0.1% / ±1%
- 20.0% to 100% / 0.1% / ±3% of reading ±5%
- 100% to 999.9% / 0.1% / ±10% of reading ±10%
|
Maximum Measurement of AC Voltage and Current | - 50 Hz / 19 µS / ±5% ±30 digits
- 60 Hz / 16 µS / ±5% ±30 digits
|
Peak Value Measurement of AC Voltage and Current | 1.00 to 99.99 / 0.01 / ±5% ±30 digits |
The Frequency Range in Automatic Mode | 45 Hz to 65 Hz / 0.1 H z / 0.1 Hz |
Memory | 512 kB for a maximum 52,420 readings taken by 1 phase / 2 conductors |
Port | USB |
Software and Cable | Yes, for Windows 2000, XP, ME |
Display | Backlit LCD with dot-matrix |
Power | 8 AA batteries (Mignon) |
Dimensions | 257 mm x 155 mm x 57 mm 10.1 in x 6.10 in x 2.24 in |
Weight | 1.16 kg / 2.56 lbs |
Operating Conditions | max. 85% relative humidity -10° C to 50° C / 14° F to 122° F |
Type of Protection / Standards | IEC 61010, 600 V/CAT III |