Product Characteristics |
Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
Process Connection | Threaded connection G 2 DN50 flat seal |
System | Gold-plated contacts |
Application | Totalizer function; empty pipe detection; for industrial applications |
Installation | Connection to pipe by means of an adapter |
Media | Conductive liquids; water; water-based media |
Medium Temperature [° C] | -10 - 90 |
Pressure Rating [bar] | 16 |
Pressure Rating [MPa] | 1.6 |
MAWP (for Applications According to CRN) [bar] | 16 |
Electrical Data |
Operating Voltage [V] | 18 - 32 DC; (to SELV/PELV) |
Current Consumption [mA] | < 150 |
Protection Class | III |
Reverse Polarity Protection | Yes |
Power-on Delay Time [s] | 5 |
Inputs / Outputs |
Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
Inputs |
Inputs | Counter reset |
Outputs |
Total Number of Outputs | 2 |
Output Signal | Switching signal; analog signal; pulse signal; frequency signal; IO-Link; (configurable) |
Electrical Design | PNP/NPN |
Number of Digital Outputs | 2 |
Output Function | Normally open / closed; (configurable) |
Maximum Voltage Drop Switching Output DC [V] | 2 |
Permanent Current Rating of Switching Output DC [mA] | 250; (per output) |
Number of Analog Outputs | 1 |
Analog Current Output [mA] | 4 - 20; (scalable) |
Maximum Load [Ω ] | 500 |
Analog Voltage Output [V] | 0 - 10; (scalable) |
Minimum Load Resistance [Ω ] | 2000 |
Pulse output | Flow rate meter |
Short-Circuit Protection | Yes |
Type of Short-Circuit Protection | Yes (non-latching) |
Overload Protection | Yes |
Frequency of the output [Hz] | 0.1 - 10000 |
Measuring/Setting Range |
Measuring dynamics | 1: 60 |
Volumetric flow quantity monitoring |
Pulse value | 0.0001 - 300 x 10³ m³ |
In steps of | 0.0001 m³ |
Pulse length [s] | 0,016 - 2 |
Temperature Monitoring |
Measuring Range [° C] | -20 - 80 |
Display range [° C] | -40 - 100 |
Resolution [° C] | 0.2 |
Set point SP [° C] | -19.2 - 80 |
Reset point rP [° C] | -19.6 - 79.6 |
Analog Start Point [° C] | -20 - 60 |
Analog End Point [° C] | 0 - 80 |
In Steps of [° C] | 0.2 |
Accuracy / deviations Flow monitoring |
Accuracy (in the Measuring Range) | ± (0,8 % MW + 0,5 % MEW) |
Repeatability | ± 0,2% MEW |
Temperature Monitoring |
Temperature Drift | ± 0,0333 ° C / K |
Accuracy [K] | ± 1 (25 ° C; Q>15 l/min) |
Reaction Times Flow monitoring |
Response Time [s] | 0.35; (dAP = 0) |
Delay Time Programmable dS, dr [s] | 0 - 50 |
Damping Process Value dAP [s] | 0 - 5 |
Temperature Monitoring |
Dynamic Response T05 / T09 [s] | T09 = 3 (Q>15 l/min) |
Software / Programming |
Parameter Setting | Flow monitoring; quantity meter; Preset counter; Temperature Monitoring; hysteresis / window; normally open / closed; switching logic; current/voltage/frequency/pulse output; Start-up delay; display can be deactivated; Display Unit; empty pipe detection |
Interfaces |
Communication Interface | IO-Link |
Transmission Type | COM2 (38,4 kBaud) |
IO-Link Revision | 1.1 |
SDCI Standard | IEC 61131-9 CDV |
Profiles | Smart Sensor: Process Data Variable; Device Identification |
SIO Mode | Yes |
Required Master Port Class | A |
Process Data Analog | 3 |
Process Data Binary | 2 |
Minimum Process Cycle Time [ms] | 5 |
Operating Conditions |
Ambient Temperature [° C] | -10 - 60 |
Storage Temperature [° C] | -25 - 80 |
Protection | |
MTTF [Years] | 85 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical Data |
Weight [g] | 3176 |
Material | Stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U |
Materials (Wetted Parts) | Stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEEK; Centellen; FKM |
Process Connection | Threaded connection G 2 DN50 flat seal |