| Product Characteristics |
| Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
| Process Connection | Threaded connection Rp 3/4 Internal thread |
| System | Gold-plated contacts |
| Media | Liquids; water; glycol solutions; Coolants |
| Medium Temperature [° C] | -10 - 100 |
| Pressure Rating [bar] | 40 |
| Pressure Rating [MPa] | 4 |
| MAWP (for Applications According to CRN) [bar] | 40 |
| Electrical Data |
| Operating Voltage [V] | 18 - 30 DC; (to SELV/PELV) |
| Current Consumption [mA] | < 50 |
| Protection Class | III |
| Reverse Polarity Protection | Yes |
| Power-on Delay Time [s] | < 3 |
| Inputs / Outputs |
| Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
| Outputs |
| Total Number of Outputs | 2 |
| Output Signal | Switching signal; analog signal; frequency signal; IO-Link; (configurable) |
| Number of Digital Outputs | 2 |
| Output Function | Normally open / closed; (configurable) |
| Maximum Voltage Drop Switching Output DC [V] | 2 |
| Permanent Current Rating of Switching Output DC [mA] | 150; (per output 2 x 200 ( - 60 ° C); 2 x 250 ( - 40 ° C)) |
| Switching cycles (mechanical) | 10 million |
| Number of Analog Outputs | 1 |
| Analog Current Output [mA] | 4 - 20 |
| Maximum Load [Ω ] | 500 |
| Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Frequency of the output [Hz] | 0 - 10000 |
| Measuring/Setting Range |
| Frequency at the end point FRP [Hz] | 10 - 10000 |
| Measuring dynamics | 1: 50 |
| Temperature Monitoring |
| Measuring Range [° C] | -10 - 100 |
| Display range [° C] | -32 - 122 |
| Resolution [° C] | 1 |
| Set point SP [° C] | -9 - 100 |
| Reset point rP [° C] | -10 - 99 |
| In Steps of [° C] | 1 |
| Frequency start point, FSP [° C] | -10 - 78 |
| Frequency end point, FEP [° C] | 12 - 100 |
| Frequency at the end point FRP [Hz] | 10 - 10000 |
| Accuracy / deviations Flow monitoring |
| Accuracy (in the Measuring Range) | ± (4 % MW + 1 % MEW); (Q>0,5 l/min; medium and operating temperature: +22 ° C ± 4K) |
| Repeatability | ± 1 % MEW |
| Temperature Monitoring |
| Temperature Drift | 0,029 ° C / K |
| Accuracy [K] | 3 K (25° C; Q>1 l/min) |
| Reaction Times Flow monitoring |
| Response Time [s] | 0.01 |
| Damping Process Value dAP [s] | 0 - 5 |
| Damping for the Analog Output dAA [s] | 0 - 5 |
| Temperature Monitoring |
| Dynamic Response T05 / T09 [s] | T09 = 120 (Q>1 l/min) |
| Software / Programming |
| Parameter Setting | Hysteresis / window; normally open / closed; switching logic; current/frequency output; medium selection; damping for the switching output / analog output; display can be rotated and switched off; standard unit of measurement; process value color |
| Interfaces |
| Communication Interface | IO-Link |
| Transmission Type | COM2 (38,4 kBaud) |
| IO-Link Revision | 1.1 |
| SDCI Standard | IEC 61131-9 CDV |
| Profiles | Smart Sensor: Process Data Variable; Device Identification |
| SIO Mode | Yes |
| Required Master Port Class | A |
| Process Data Analog | 2 |
| Process Data Binary | 2 |
| Minimum Process Cycle Time [ms] | 5 |
| Operating Conditions |
| Ambient Temperature [° C] | 0 - 60 |
| Storage Temperature [° C] | -15 - 80 |
| Protection | |
| MTTF [Years] | 145 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Mechanical Data |
| Weight [g] | 734.1 |
| Material | Stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated |
| Materials (Wetted Parts) | Stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; O-ring: FKM |
| Process Connection | Threaded connection Rp 3/4 Internal thread |
| Notes | Please note the changed housing design! |
| Electrical Connection |
| Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |