Product Characteristics |
Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
Measuring range [psi] | -15 - 15 |
Process Connection | Threaded connection 1/4" NPT Internal thread |
System | Gold-plated contacts |
Media | Liquids and gases |
Medium Temperature [° C] | -25 - 80 |
Min. bursting pressure [psi] | 725 |
Pressure rating [psi] | 290 |
Type of Pressure | Relative pressure |
Electrical Data |
Operating Voltage [V] | 18 - 32 DC; (to SELV/PELV) |
Current Consumption [mA] | < 35 |
Minimum Insulation Resistance [MΩ ] | 100; (500 V DC) |
Protection Class | III |
Reverse Polarity Protection | Yes |
Power-on Delay Time [s] | 0.3 |
Integrated Watchdog | Yes |
Inputs / Outputs |
Number of Inputs and Outputs | Number of Digital Outputs: 2Number of Analog Outputs: 1 |
Outputs |
Total Number of Outputs | 2 |
Output Signal | Switching signal; analog signal; (configurable) |
Electrical Design | PNP/NPN |
Number of Digital Outputs | 2 |
Output Function | Normally open / closed; (configurable) |
Maximum Voltage Drop Switching Output DC [V] | 2 |
Permanent Current Rating of Switching Output DC [mA] | 250 |
Switching Frequency DC [Hz] | < 500 |
Number of Analog Outputs | 1 |
Analog Current Output [mA] | 4 - 20; (scalable 1: 4) |
Maximum Load [Ω ] | (Ub - 10 V) / 20 mA |
Analog Voltage Output [V] | 0 - 10; (scalable 1: 4) |
Minimum Load Resistance [Ω ] | 2000 |
Short-Circuit Protection | Yes |
Type of Short-Circuit Protection | Yes (non-latching) |
Overload Protection | Yes |
Measuring/Setting Range |
Measuring range [psi] | -15 - 15 |
Set point SP [psi] | -14.8 - 15 |
Reset point rP [psi] | -14.9 - 14.9 |
Analog start point [psi] | -15 - 7.5 |
Analog end point [psi] | -7.5 - 15 |
In steps of [psi] | 0.1 |
Accuracy / Deviations |
Switch Point Accuracy [% of the Span] | < ± 0,4; (Turn down 1: 1) |
Repeatability [% of the Span] | < ± 0,1; (with temperature fluctuations<10 K; Turn down 1: 1) |
Characteristics Deviation [% of the Span] | < ± 0,25 (BFSL) /<± 0,5 (LS); (Turn down 1: 1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis Deviation [% of the Span] | < ± 0,1; (Turn down 1: 1) |
Long-Term Stability [% of the Span] | < ± 0,1; (Turn down 1: 1; per year) |
Temperature coefficient Zero Point [% of the Span / 10 K] | < ± 0,2; (-25 - 80 ° C) |
Temperature Coefficient Span [% of the Span / 10 K] | < ± 0,2; (-25 - 80 ° C) |
Reaction Times |
Response Time [ms] | < 1.5 |
Damping Process Value dAP [s] | 0.01 - 4 |
Damping for the Analog Output dAA [s] | 0.01 - 4 |
Maximum Response Time Analog Output [ms] | 3 |
Software / Programming |
Parameter Setting | Hysteresis / window; normally open / closed; switching logic; current/voltage output; Damping; adaptation of displayed values; display can be rotated and switched off; Display Unit; Zero point; span |
Operating Conditions |
Ambient Temperature [° C] | -25 - 80 |
Storage Temperature [° C] | -40 - 100 |
Protection | IP 65 |
MTTF [Years] | 167.14 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical Data |
Weight [g] | 256.5 |
Material | Stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
Materials (Wetted Parts) | Stainless steel (1.4305 / 303); ceramics; FKM |
Minimum Pressure Cycles | 100 million |
Process Connection | Threaded connection 1/4" NPT Internal thread |
Restrictor Element Integrated | No (can be retrofitted) |
Display Unit | Mbar; kPa; psi; inH2O; inHg |
Electrical Connection |
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |