Product Characteristics |
Number of Inputs and Outputs | Number of Digital Outputs: 1 |
Process Connection | Threaded connection 1/4" NPT Internal thread |
Media | liquids and gases |
Conditionally Suitable for | Use in gases at pressures>25 bar only on request |
Medium Temperature [°C] | -25 - 80 |
Type of Pressure | Relative pressure |
Electrical Data |
Operating Voltage Tolerance [%] | 5 - 10 |
Operating Voltage [V] | 90 - 250 AC |
Nominal Voltage AC [V] | <250 |
Current Consumption [mA] | <10 |
Minimum Insulation Resistance [MΩ] | 100; (500 V DC) |
Protection Class | II |
Reverse Polarity Protection | No |
Power-on Delay Time [s] | 0.2 |
Integrated Watchdog | Yes |
Inputs / Outputs |
Number of Inputs and Outputs | Number of Digital Outputs: 1 |
Outputs |
Total Number of Outputs | 1 |
Output Signal | Switching signal |
Electrical Design | Triac |
Number of Digital Outputs | 1 |
Output Function | Normally open / closed; (configurable) |
Maximum Voltage Drop Switching Output AC [V] | 2 |
Permanent Current Rating of Switching Output AC [mA] | 250; (( - 70 °C) 1000 ( - 60 °C) 1500 ( - 45 °C) 2500 ( - 20 °C)) |
Switching Frequency AC [Hz] | <160 |
Short-circuit proof | No |
Overload Protection | No |
Accuracy / Deviations |
Switch Point Accuracy [% of the Span] | ± 1,0 |
Repeatability [% of the Span] | ± 0,1; (with temperature fluctuations<10 K) |
Linearity Deviation [% of the span] | ± 0,5 |
Hysteresis Deviation [% of the Span] | ± 0,1 |
Long-Term Stability [% of the Span] | ± 0,1; (per year) |
Temperature coefficient Zero Point [% of the Span / 10 K] | ± 0,2; (-25 - 80 °C) |
Temperature Coefficient Span [% of the Span / 10 K] | ± 0,3; (-25 - 80 °C) |
Reaction Times |
Delay Time Programmable dS, dr [s] | 0, 0,2, - 10, 11, - 50 |
Damping Process Value dAP [s] | 0 - 4 |
Software / Programming |
Adjustment of the switch point | Programming button |
Parameter Setting | Hysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display Unit |
Operating Conditions |
Ambient Temperature [°C] | -25 - 80 |
Storage Temperature [°C] | -40 - 100 |
Protection | IP 67 |
MTTF [Years] | 225 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical Data |
Weight [g] | 358.4 |
Material | Stainless steel (1.4301 / 304); PC; PBT; PA; FKM |
Materials (Wetted Parts) | Stainless steel (1.4305 / 303); ceramics; FKM |
Minimum Pressure Cycles | 100 million |
Process Connection | Threaded connection 1/4" NPT Internal thread |
Restrictor Element Integrated | No (can be retrofitted) |
Electrical Connection |
Required Protection | Miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
Electrical Connection |
Connection | Connector: 1 x 1/2"; coding: C |