Product Characteristics |
Number of Inputs and Outputs | Number of Digital Outputs: 2 |
Process Connection | Threaded connection G 1/4 Internal thread |
System | gold-plated contacts |
Media | liquids and gases |
Medium Temperature [°C] | -20 - 60 |
Type of Pressure | Relative pressure; vacuum |
Electrical Data |
Operating Voltage [V] | 18 - 36 DC; (to SELV/PELV) |
Current Consumption [mA] | <50 |
Protection Class | III |
Reverse Polarity Protection | Yes |
Overvoltage protection | Yes; (<40 V) |
Power-on Delay Time [s] | 0.3 |
Integrated Watchdog | Yes |
Inputs / Outputs |
Number of Inputs and Outputs | Number of Digital Outputs: 2 |
Outputs |
Total Number of Outputs | 2 |
Output Signal | Switching signal; IO-Link; (configurable) |
Electrical Design | PNP/NPN |
Number of Digital Outputs | 2 |
Output Function | Normally open / closed; (configurable) |
Maximum Voltage Drop Switching Output DC [V] | 2 |
Permanent Current Rating of Switching Output DC [mA] | 250 |
Switching Frequency DC [Hz] | <170 |
Short-Circuit Protection | Yes |
Type of Short-Circuit Protection | Yes (non-latching) |
Accuracy / Deviations |
Switch Point Accuracy [% of the Span] | ± 0,5 |
Repeatability [% of the Span] | ± 0,1; (with temperature fluctuations<10 K) |
Characteristics Deviation [% of the Span] | ± 0,25 (BFSL) /<± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis Deviation [% of the Span] | ± 0,25 |
Long-Term Stability [% of the Span] | ± 0,05; (per 6 months) |
Temperature coefficient Zero Point [% of the Span / 10 K] | 0,2; (0 - 60 °C) |
Temperature Coefficient Span [% of the Span / 10 K] | 0,2; (0 - 60 °C) |
Reaction Times |
Delay Time Programmable dS, dr [s] | 0; 0,2 - 50 |
Software / Programming |
Parameter Setting | Hysteresis / window; normally open / closed; Diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display Unit |
Interfaces |
Communication Interface | IO-Link |
Transmission Type | COM2 (38,4 kBaud) |
IO-Link Revision | 1.1 |
SDCI Standard | IEC 61131-9 CDV |
Profiles | No profile |
SIO Mode | Yes |
Required Master Port Class | A |
Process Data Analog | 1 |
Process Data Binary | 2 |
Minimum Process Cycle Time [ms] | 2.3 |
Operating Conditions |
Ambient Temperature [°C] | -20 - 60 |
Storage Temperature [°C] | -40 - 100 |
Protection | IP 65 |
Tests / Approvals |
ATEX marking | II 3D Ex tc IIIC T80°C Dc X |
MTTF [Years] | 194 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical Data |
Weight [g] | 304 |
Material | Stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PEI; FKM; EPDM/X; PTFE |
Materials (Wetted Parts) | Stainless steel (1.4305 / 303); ceramics; FKM |
Minimum Pressure Cycles | 100 million |
Process Connection | Threaded connection G 1/4 Internal thread |
Restrictor Element Integrated | No (can be retrofitted) |
Electrical Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |