Generator |
Rated maximum continuous power capacity (LP) | 20,000 Watts |
Rated maximum continuous power capacity (NG) | 17,000 Watts |
Rated voltage | 208 |
Rated maximum continuous load current – 208 volts (LP / NG) | 69.4/59.0 |
Total Harmonic Distortion | Less than 5% |
Main line circuit breaker | 80 Amp |
Phase | 3 |
Number of rotor poles | 2 |
Rated AC frequency | 60Hz |
Power Factor | 0.8 |
Unit weight (lb / kg) | 466 / 211 |
Dimensions (L x W x H) in / cm | 48 x 25 x 29 / 1218 x 638 x 732 |
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load | 67 |
Sound output in dB(A) at 23 ft (7 m) with generator in Quiet-Test™ low-speed exercise mode | 58 |
Exercise duration | 5 min |
Engine |
Engine type | GENERAC G-Force 1000 Series |
Number of cylinders | 2 |
Displacement | 999 cc |
Cylinder block | Aluminum w/ Cast Iron Sleeve |
Valve arrangement | Overhead valve |
Ignition system | Solid-state w/ Magneto |
Governor system | Electronic |
Compression ratio | 9.5:1 |
Starter | 12 VDC |
Oil capacity including filter | Approx. 1.9 qt/1.9 L |
Operating rpm | 3,600 |
Controls |
Two-line plain text multilingual LCD | Simple user interface for ease of operation |
Mode buttons: |
AUTO | Automatic Start on Utility failure. 7 day exerciser. |
OFF | Stops unit. Power is removed. Control and charger still operate |
MANUAL | Start with starter control, unit stays on. If utility fails, transfer to load takes place. |
Ready to Run/Maintenance messages | Standard |
Engine run hours indication | Standard |
Programmable start delay between 2–1500 seconds | Standard (programmable by dealer only) |
Utility Voltage Loss/Return to Utility adjustable (brownout setting) | From 121-148 V/175-187 V |
Future Set Capable Exerciser/Exercise Set Error warning | Standard |
Run/Alarm/Maintenance logs | 50 events each |
Engine start sequence | Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) |
Starter lock-out | Starter cannot re-engage until five seconds after engine has stopped |
Smart Battery Charger | Standard |
Charger Fault/Missing AC warning | Standard |
Low Battery/Battery Problem Protection and Battery Condition indication | Standard |
Automatic Voltage Regulation with Over and Under Voltage Protection | Standard |
Under-Frequency/Overload/Stepper Overcurrent Protection | Standard |
Safety Fused/Fuse Problem Protection | Standard |
Automatic Low Oil Pressure/High Oil Temperature Shutdown | Standard |
Overcrank/Overspeed ( at 72 Hz)/rpm Sense Loss Shutdown | Standard |
High Engine Temperature Shutdown | Standard |
Internal Fault/Incorrect Wiring protection | Standard |
Common external fault capability | Standard |
Field upgradable firmware | Standard |