Power Input | 11-40 VDC / 20-28 VAC, 47-63Hz |
Output 1 | Form A Relay |
Signal Input |
Type | Thermocouple (J, K, T, E, B, R, S, N, L, U, P, C, D), RTD(PT100(DIN), PT100(JIS)), Current(mA), Voltage (V, mV) |
Resolution | 18 Bits |
Sampling Rate | 5 Times / Second (200msec) |
Maximum Rating | -2VDC minimum, 12VDC maximum |
Temperature Effect | 1.5µV /°C for all inputs except mA input, 3.0µV /°C for mA |
Sensor Lead Resistance Effect Thermocouple | 0.2 µV /°Ω |
Sensor Lead Resistance Effect 3-wire RTD | 2.6°C /Ω of Difference of Resistance of two leads |
Sensor Lead Resistance Effect 2-wire RTD | 2.6°C /Ω of Sum of Resistance of two leads |
Burn-out Current | 200nA |
CMRR | 120 dB |
NMRR | 55dB |
Sensor Break Detection | Sensor open for Thermocouple, RTD and mV inputs, Sensor short for RTD input, Below 1mA for 4-20mA input, Below 0.25VDC for 1 - 5VDC input. |
Sensor Break Response Time | Within 4 seconds for Thermocouple, RTD and mV inputs, 0.1 second for 4-20mA and 1 - 5VDC inputs |
Remote Set Point Input |
Type | Linear Current, Linear Voltage |
Range | -3mA to 27mA, -1.3VDC to 11.5VDC |
Accuracy | ±0.05 % |
Input Impedance | Current: 2.5Ω, Voltage:1.5MΩ |
Resolution | 18 Bits |
Sampling Rate | 1.66 Times/Second |
Maximum Rating | 280mA maximum for Current Input, 12VDC Maximum for Voltage Input |
Temperature Effect | ±1.5µV/°C for Voltage Input, ±3.0µV/°C for Current Input |
Sensor Break Detection | Below 1mA for 4-20mA input, Below 0.25VDC for 1 - 5VDC input. |
Sensor Break Responding Time | 0.1 Second |
Event Input |
Number of Event Inputs | 1 |
Logic Low | -10VDC minimum, 0.8VDC maximum |
Logic High | 2VDC minimum, 10VDC maximum |
CT Input |
CT Type | CT98-1 |
Accuracy | ±5%of Full-scale Reading ±1 Digit |
Input Impedance | 294Ω |
Measurement Range | 0 to 50AAC |
Output of CT | 0 to 5VDC |
Sampling Rate | 1 Time/Second |
Environmental and Physical Specifications |
Operating Temperature | -10°C to 50°C |
Storage Temperature | -40°C to 60°C |
Humidity | 0 to 90 % RH (Non-Condensing) |
Altitude | 2000 Meters Maximum |
Pollution | Degree II |
Insulation Resistance | 20MΩ Minimum (500V DC) |
Dielectric Strength | 2000VAC,50/60 Hz for 1 Minute |
Vibration Resistance | 10 to 55 Hz, 10m/s2 for 2 Hours |
Shock Resistance | 200 m/s2 (20g) |
Housing | Flame Retardant Polycarbonate |
Approval Standards |
Safety | UL61010-1, CSA 22.2 No.61010-1-12, EN61010-1 (IEC1010-1), ROHS, REACH |
Protective Class | IP50 for the front panel, IP20 for rear terminals and housing. All indoor use |
EMC | EN61326 |