Measurement function | Alternating current |
AC ampere range | 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A |
| mA / A: manual selection 3 mA / 30 mA / 300 mA: automatic selection 3 A / 30 A / 60 A: automatic selection |
Range / Resolution | 3 mA / 0.001 mA |
30 mA / 0.01 mA |
300 mA / 0.1 mA |
3 A / 0.001 A |
30 A / 0.01 A |
60 A / 0.1 A |
Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)² | 3 mA – 30 A 60 A | 1% + 5 digits 2% + 5 digits |
Frequency | 40 Hz to 1 kHz |
Crest Factor | 3 |
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%. The minimum value is 10 μA rms. ²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1 |
Physical |
Display (LCD) | Digital readout: 3300 count |
Display refresh rate | 4 times / sec |
Maximum conductor diameter | 40 mm |
Dimensions | 234 x 101 x 46 mm |
Weight | 500 g |
Battery | 2 AA, IEC LR6, NEDA 15A, alkaline |
Battery life | Expected battery life, without using backlight and spotlight, is more than 150 hours |
Automatic shut-down | Meter automatically shuts down after 15 minutes of inactivity |
Safety and Environmental Specifications |
General safety | IEC 61010-1: Pollution Degree 2 |
Measurement safety | IEC 61010-2-032: CAT III 600 V / CAT IV 300 V |
Operating temperature | -10 °C to +50 °C |
Storage temperature | -40 °C to +60 °C |
Operating humidity | Non-condensing (<10 °C) |
90% relative humidity (10 °C to 30 °C) |
75% relative humidity (30 °C to 40 °C) |
45% relative humidity (40 °C to 50 °C) |
Protection class | IEC 60529: IP30 (jaw closed) |
Operating altitude | 2000 m |
Storage altitude | 12000 m |
Current sensor action category | IEC 61557-13: Class 2, ≤30 A / m |
Electromagnetic compatibility (EMC) |
International |
IEC 61326-1 | Industrial Electromagnetic Environment |
CISPR 11 | Group 1 Class B |
Group 1 | Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device's own internal functions is essential. |
Class B | Equipment for home appliances and residential buildings directly connected to a low voltage power supply network equipment. When this device is connected to a test object, it may exceed the emission levels produced by CISPR 11 requirements. Korea (KCC): A type of equipment (radio and communication equipment industry) |
Class A | This product meets the requirements of industrial electromagnetic equipment, vendors or users should be aware of this. This device is intended for use in a commercial environment, instead of the home environment. USA (FCC): 47 CFR 15 B Subpart. In accordance with section 15.103 provides that the products are considered tax-free device. |