Environmental |
Operating Temperature | 32 to 113°F (0 to 45°C) |
Storage Temperature | -4C to 140°F (<20 to 60°C), with battery: -4 to 122°F (-20 to 50°C) |
Operating Humidity | - <50°F (<10°C) non condensing
- 50 to 86°F (10 to 30°C) ≤95%
- 86 to 104°F (30 to 40°C) ≤75%
- 104 to 113°F (40 to 45°C) ≤45%
|
Operating Altitude | 6500' (2000 m) (up to 4,000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
Storage Altitude | 39,000' (12,000 m) |
IP Rating | IEC 60529:IP50, in connected condition with protection caps in place |
Vibration | MIL-T-28800E, Type 3, Class III, Style B |
Safety IEC 61010-1 | - IEC mains input: Overvoltage Category II, Pollution Degree 2
- Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
|
Electromagnetic Compatibility (EMC) | - International: IEC 61326-1: Industrial
- Korea (KCC): Class A Equipment (Industrial Broadcasting & Communication Equipment)
- USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
|
Wireless Radio with Adapter | - Frequency range: 2412 to 2462 MHz
- Output power: <100 mW
|
Electrical |
Single and Three-Phase Topologies | Wiring configurations: 1-φ, 1-φ IT, Split-phase, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ delta, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, 3-φ high leg delta, 3-φ delta balanced. Currents only (load studies) |
Voltage Inputs | - Number of inputs: 4 (3 phases and neutral)
- Maximum input voltage: 1000 Vrms (1700 Vpk) phase to neutral
|
Input Impedance | 10 MΩ each phase to neutral |
Bandwidth | 42.5 Hz to 3.5 kHz |
Scaling | 1:1, variable |
Current Inputs | Number of inputs: 3, mode selected automatically for attached sensor |
Current Sensor Output Voltage | - Clamp: 500 mVrms / 50 mVrms; CF 2.8
- Rogowski coil: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
|
Bandwidth (-3 dB) | 42.5 Hz to 3.5 kHz |
Scaling | 1:1 and variable |
Data Acquisition Resolution | 16-bit synchronous sampling |
Sampling Frequency | 10.24 kHz at 50/60Hz, synchronized to mains frequency |
Input Signal Frequency | Mains 50/60 Hz (42.5 to 69 Hz) |
Data Storage | Internal flash memory (not user replaceable) |
Memory Size | Typical 1 offline logging session of 1 week with 1 second intervals. The number of possible logging sessions and logging period depends on user requirements. |
Measured Parameters | Voltage, current, frequency, THD V, THD A, power, power factor, fundamental power, DPF |
Averaging Interval | 1 s |
Total Harmonic Distortion | THD for voltage and current is calculated on 25 harmonics |
Calculated min/max values times | - Voltage: Full cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz)
- Current: Half cycle RMS (10 ms at 50 Hz, 8.3 ms at 60 Hz)
- Power: 200 ms
|
Interfaces | USB-A: Firmware updates, max. supply current: 120 mA |
WiFi | Supported modes: Direct connection and connection to infrastructure |
Security | WPA2-AES with pre-shared key |
Power Supply | Voltage Range: Nominal 100 V to 500 V (85 V min to 550 V max) using safety plug input |
Mains Power | Nominal 100 V to 240 V (85 V min to 265 V max) using IEC 60320 C7 input |
Power Consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
Standby Power | <0.3 W only when powered using IEC 60320 input |
Efficiency | ≥68.2 % (in accordance with energy efficiency regulations) |
Mains Frequency | 50/60 Hz ±15 % |
Battery Power | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
On-Battery Runtime | Up to 4 hr (up to 5.5 hr in energy saving mode) |
Charging Time | <6 hours |
General |
Color LCD Display | 4.3-inch active matrix color TFT, 480 pixels x 272 pixels, resistive touch panel |
Dimensions | 7.8 x 6.6 x 4.0" (19.8 x 16.7 x 9 cm) |
Weight | 2.5 lb (1.1kg) |
Tamper Protection | Kensington lock |