Accuracy | ±5% of the LEL reading up to 50% LEL |
Alarm | Audible buzzer, output relay 0.5A 200 V, 10 VA |
Alarm Relay Actuation | Selectable N.O. default or N.C. |
Alarm Relay Settings | OFF, 5, 10, 15, 20 (default), 25% LEL |
Current at 24VDC | 775 mA in alarm (two relays), 50 mA (fan relay only), and 23 mA standby |
Fan Relay | 5 A, 240 VAC, pilot duty, SPDT |
Fan Relay Actuation | Selectable at 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 (default), 11, 12, 13, 14, 15, 16, 17, 18, 19, 20% LEL |
Fan Delay Settings | 0, 1, 3 (default), 5, 10 minutes |
Fan Minimum Run Time | Settings are OFF (default), 3, 5, 10, 15 minutes |
Current Loop | 4 - 20 mA for 0 - 50% LEL |
Operating Environment | - Temperature: -18 - 52 °C / 0 - 125 °F
- Relative Humidity: 10 - 90%
|
Relative Humidity | 10 - 90% |
Power Requirements | 3 W (max) from 12 - 24 VAC, 12 - 48 VDC |
Dimensions / Weight | 114 x 114 x 53 mm (4.5 x 4 x 2.1 in) / 500 g (1 lb) |