ATC Diversified, CLB-120-ALE-5, 1.0 to 5.0 Amps Three Phase Current Unbalance and Over Current Monitor/Relay
Features:
- AC over the current monitor
- Automatic reset
The CLB Series is designed to protect three-phase equipment against constant unbalanced and CURRENT conditions. The control voltage is continuously applied to supply the sensing circuitry and the internal relay. When the current of any phase approximately 20% above the maximum operating current, the inrush delay begins. This delay disables the over-current sensors while high inrush currents are present. Any time the currents are outside the preset limits after completion of the inrush delay, the internal relay will de-energize (drop out). A 2% differential (hysteresis) between pickup and Drop-out is incorporated to prevent chattering when operated in the automatic reset mode and the current is at the trip point.
The reset mode is selected as follows:
- AUTOMATIC: Place a jumper between pins ten (10) and eleven (11).
- MANUAL: Place a normally open switch between pins ten (10) and eleven (11).
When there is a loss and reapplication of the control voltage, the external switch must be closed before the circuit will again become operative. An External CT may be used to extend the range of the Current Monitor.
For more information, please see Data Sheet