Control 1 Output Specifications |
Contact Rating (SPST | 5a at 230VAC / 30VDC resistive |
SSR Drive (Voltage Pulse) | 18VDC 20ma |
Current | 0/4 to 20ma dc (loop impedence 500 ohms max |
Voltage | 0 to 5/10 VDC (load resistance 10K ohms min) |
Alarm 2 Output Specification |
Contact Rating (SPST) | 5a at 230VAC / 30VDC resistive |
SSR DRIVE | 12VDC 20ma |
Functional Specification |
Control Action | PID, On-Of |
Proportional Band (P) | 0.0 to 400.0 deg |
Integral Time (I) | 0 to 3600 sec |
Derivative Time (D) | 0 to 200 sec |
Cycle Time | 0.1 to 100.0 sec |
Hysteresis Width | 0.1 to 99.9 deg |
Manual Reset Value | 99.9 to 99.9 deg |
Heat Cool Pid |
Control Action | PID |
Cycle Time | 0.1 to 100 sec |
Proportional Gain | 0.0 to 400.0 deg |
Deadband | Programmable from setpoint low limit to setpoint high limit |
Alarms |
Modes | Deviation high/low, Absolute high/low, band, sensor break |
Hysterisis | 0.1 to 99.9 deg |
Ramp Soak |
Ramp Rage | 1 to 9999 deg/hr. |
Soak Time | 0 to 1440 min |
Soft Start Time | 0 to 999 min |
Supply Voltage | 85 to 270V AC/DC (50/60 Hz) |
Power Consumption | 6VA max at 230 VAC |
Retransmission |
Current | 0/4 to 20ma DC (loop impedence 500 ohms max) |
Voltage | 0 to 5/10V DC (load resistance 10k ohms min) |
Update Rate | 100msec |
Serial Communication |
Interface Standard | RS485 |
Communication Address | 1 to 99, maximum of 32 units per line |
Transmission mode | Half duplex |
Transmission protocol | MODBUS RTU |
Transmission distance | 500 m maximum |
Transmission speed | 9600, 4800, 1200, 600, 300 bits/sec. |
Temperature |
Operating | 0 to 50°C (32 to 122°F) |
Storage | -20 to 75°C (-4 to 167°F) |
Humidity (Non Condensing) | 95% RH |
Weight | 6.4 oz |
Protection Level | IP65 for faceplate |
Digits | - 4 digit, 7 segment LED Dual Display
- Height of Upper display: 0.3785"
- Height of Lower display: 0.2720"
|
Led indications | Relay On, Alarm, Manual Mode, Tune |
Inputs | - Thermocouple (J,K,T,R,S,C,E,B,N,L,U,W)
- Platinel II, RTD (Pt100)
- DC Analog Inputs (-5 to 56mv, 0 to 10v, 0 to 20 ma)
|
Sampling Time | 200 ms |
Input Filter (FTC) | 0.2 to 10.0 sec |
Resolution | - 1/0.1 deg for TC/RTD only
- Fixed 1 deg resolution for R&S Type TC)
- Decimal point position selectable: 1/0.1/0.01/0.001 for analog input
|
Temperature Unit | C/F deg selectable |
Indication ACC: | - For TC inputs 0.25% of F.S. ± 1°
- R&S type TC inputs 0.5% of F.S. ± 2 deg (20 min of warm up time for TC inputs)
- For RTD inputs 0.1% of F.S. ± 1 deg
- For Analog Input ± 0.5%, ± 1 digit
|